Example commercial lease-end condition report - New York

A complete fictional inspection showing how PropertySurvey Pro can organise scope, evidence, condition items, actions and cost allowances.

Metro Envelope Consulting

Commercial property condition and technical inspections

120 Example Avenue, New York, NY 10017

[email protected]

www.metro-envelope.example

Commercial Lease-End Condition Report

Client

East River Workspace LLC

Commercial tenant approaching lease expiry

Property

Suite 42B, 245 Example Avenue, New York, NY 10017

Tenant lease-end condition instruction

ReferenceMEC-2026-0620
Instruction15 Jun 2026
Survey20 Jun 2026
Report22 Jun 2026
Property description

12,000 ft² office suite within a steel-and-concrete framed commercial building

Prepared by

Avery Brooks

Commercial building inspector

Company History

Metro Envelope Consulting is a fictional independent building consultancy providing commercial condition inspections and technical due-diligence support. Its reports record observed condition, limitations and proposed next actions without determining legal liability.

Metro Envelope Consulting

Commercial property condition and technical inspections

120 Example Avenue, New York, NY 10017

[email protected]

www.metro-envelope.example

Legal Disclaimer

This report records a visual, non-destructive inspection of the accessible areas described. It is not legal advice, a lease interpretation, code certification, structural design, environmental assessment or valuation. Observed condition items must be reviewed against the executed lease, approvals and applicable law by the client's legal and technical advisers.

Client Instructions

Record the visible condition of the leased office suite before expiry; identify tenant alterations and repair items that may require review; attach location and photographic context; and provide preliminary budget allowances for client planning. No determination of breach or liability was requested.

Executive Summary

The suite was generally operational and maintained, with four principal condition items requiring lease and scope review: later drywall partitions, damaged ceiling tiles and grid components, altered HVAC diffusers, and adhesive residue with local floor-screed damage.

A small number of service penetrations were visible above the suspended ceiling. Their fire-stopping and structural implications could not be confirmed visually and require record review and competent specialist inspection.

The preliminary allowance for the four measured items is $58,700 before sales tax, design, permits, professional fees and contingency. The amount is not a contractor quotation and does not determine which party is responsible.

Items are described as observed condition or assumed reinstatement scope, not as legal findings.

Metro Envelope Consulting

Commercial property condition and technical inspections

120 Example Avenue, New York, NY 10017

[email protected]

www.metro-envelope.example

Scope and Definitions

Accessible office, meeting, circulation, welfare and support areas were visually inspected. Ceiling tiles were lifted at sample locations where safe and permitted. Fixed joinery, occupied storage and building-wide plant were outside the instruction.

TermMeaning in this report
Condition itemAn observed issue or alteration requiring review; not a legal conclusion.
Proposed actionA preliminary technical response subject to lease, design and contractor review.
Budget allowanceAn illustrative planning figure, not a quotation or valuation.
Not inspectedAn area or system outside the agreed scope or inaccessible at the visit.

Energy Performance Context

The landlord supplied an ENERGY STAR score for the whole building, not the demised suite. It is recorded as context only and does not certify the suite or determine the condition items in this report.

Whole-building score78
Statement year2025
Suite floor area12,000 ft²
VerificationLandlord document supplied

Metro Envelope Consulting

Commercial property condition and technical inspections

120 Example Avenue, New York, NY 10017

[email protected]

www.metro-envelope.example

Description of Property

Single office suite on the 42nd floor of a multi-tenant commercial tower. The inspected accommodation includes open-plan office space, perimeter offices, meeting rooms, reception, pantry, restrooms and support rooms. The base building is understood to be a steel frame with composite concrete floor slabs and a glazed curtain-wall envelope.

External Observations

The instruction was limited to the leased suite. Curtain-wall surfaces visible from inside showed no active leakage at the inspection. Roof, facade access systems and common external areas were not inspected.

Services Observed

  • Suspended ceiling with recessed lighting, sprinklers, detectors and HVAC diffusers.
  • Tenant-installed data cabling and local power distribution above ceiling zones.
  • Pantry plumbing visible only at accessible fixtures and cabinets.
  • No intrusive testing, air balancing, electrical testing or fire-stopping verification.

Methodology

Condition items were logged by location and element with observation, priority, proposed action, photographs and optional cost allowance. Dimensions are survey measurements for planning and must be checked before procurement.

Metro Envelope Consulting

Commercial property condition and technical inspections

120 Example Avenue, New York, NY 10017

[email protected]

www.metro-envelope.example

Floor Plan

Reception and lift lobby
Open office - marker C1
Meeting rooms
Perimeter offices
Pantry and support
Restrooms and service core
Diagrammatic suite plan - not to scale - marker C1 identifies the principal alteration area.

Weather and Property Orientation - South and East

Weather is recorded because facade leakage and external-envelope observations can depend on conditions. No active leakage was seen from the suite during the dry inspection.

ConditionsDry and partly cloudy
Temperature79°F
Humidity58%
WindSSW - 9 mph

Metro Envelope Consulting

Commercial property condition and technical inspections

120 Example Avenue, New York, NY 10017

[email protected]

www.metro-envelope.example

Site and Subsoil Context

No geotechnical investigation formed part of this lease-end suite inspection. Public mapping indicates urban made ground over regional geology, but this does not inform the internal fit-out items recorded. Foundation and below-grade areas were outside scope.

Desk-based ground data is included only as optional report context and no foundation conclusion is drawn.

On-Site Assessment Summary

Assessment areaStatusScope limit
General access and egressRoutes visually open at inspectionNot a code or fire-safety certification
Ceiling void samplesViewed at selected removable tilesNo full survey of concealed services
Moisture indicatorsNo active staining observed in inspected suiteNo facade water test
Hazardous materialsNot assessedSeparate specialist survey required if relevant
AccessibilityGeneral arrangement notedNo ADA compliance audit

Metro Envelope Consulting

Commercial property condition and technical inspections

120 Example Avenue, New York, NY 10017

[email protected]

www.metro-envelope.example

External Analysis

Curtain-wall perimeter

South and east elevations viewed internally

No active defect observed
Observation
Accessible internal perimeter seals and finishes were dry with no current staining.
Evidence
Visual inspection during dry weather; no hose or chamber test.
Interpretation
No active leakage was identified, but the inspection cannot confirm concealed seals or performance under wind-driven rain.
Recommendation
Record as inspected with no immediate action. Review landlord facade records if the lease-end scope requires envelope evidence.

Perimeter floor-box zones

East open-office bay

Local finish repair
Observation
Two floor boxes were removed, leaving local carpet-tile cuts and adhesive residue.
Recommendation
Confirm required final arrangement, make electrical points safe through the appropriate contractor and reinstate floor finishes to the agreed standard.

Metro Envelope Consulting

Commercial property condition and technical inspections

120 Example Avenue, New York, NY 10017

[email protected]

www.metro-envelope.example

Internal Room Findings

Open office - tenant partitions

Marker C1

Review for reinstatement
Partition length142 linear ft
Affected floor1,050 ft²
Photos8
PriorityBefore handback
Observation
Later non-structural drywall partitions form four cellular offices within the open-plan area. Local fixings pass through carpet tiles and the suspended ceiling grid.
Evidence
Plan mark-up, measurements and photographs MEC-C1-01 to MEC-C1-08.
Interpretation
The partitions are tenant alterations. Whether removal is required depends on the lease, approvals and landlord instruction.
Recommendation
Confirm lease-end requirement; if removal is instructed, isolate services, dismantle partitions and make good ceilings, walls and floor finishes.

Suspended ceiling

Open office and meeting rooms

Repair
Observation
Twelve stained or damaged tiles and three distorted grid sections were recorded. No active moisture was visible at the visit.
Evidence
Ceiling schedule and photographs MEC-C2-01 to MEC-C2-06.
Interpretation
The cause of historical staining is not established by appearance alone.
Recommendation
Review building leak records, confirm the area is dry and replace damaged tiles and grid components to the agreed specification.

HVAC diffuser layout

Altered office zones

Specialist review
Observation
Six diffusers appear relocated relative to the landlord plan, with flexible duct extensions visible above sample ceiling tiles.
Interpretation
Airflow performance and required reinstatement cannot be confirmed visually.
Recommendation
Compare approved drawings and obtain an HVAC contractor's scope and balancing advice before pricing final work.

Floor finishes

Former collaboration area

Repair
Observation
Adhesive residue and local screed damage affect approximately 1,800 ft² after removal of a raised finish.
Recommendation
Prepare a sample repair, confirm substrate moisture and compatibility, then grind residue, repair screed and reinstate the agreed floor finish.

Metro Envelope Consulting

Commercial property condition and technical inspections

120 Example Avenue, New York, NY 10017

[email protected]

www.metro-envelope.example

Independent Consultant Disclosure

Metro Envelope Consulting has no financial interest in any contractor appointed for the work. The figures below are fictional planning allowances based on measured example quantities. They are not current New York quotations, a valuation or a statement of recoverable loss.

Essential Summary of Costs

Contingency, phasing, after-hours working, design, permits and landlord review may materially change the final cost. Obtain current contractor pricing before reliance.

Subtotal$58,700
Sales taxExcluded
Fees and permitsExcluded
Planning allowance$58,700
Condition itemProposed actionExample allowance (USD)
Tenant partitionsRemove and make good connected finishes$18,500
Ceiling tiles and gridReplace damaged components after cause review$6,200
HVAC diffuser alterationsSpecialist review, reinstate and balance$12,000
Floor adhesive and screedPrepare substrate and reinstate carpet tile finish$22,000

Metro Envelope Consulting

Commercial property condition and technical inspections

120 Example Avenue, New York, NY 10017

[email protected]

www.metro-envelope.example

Important Notes

  • Review every condition item against the executed lease, licences for alteration, landlord approvals and photographic records.
  • Do not describe an item as a breach or assign liability without legal review.
  • Verify dimensions and quantities before procurement.
  • Obtain specialist advice for HVAC, fire-stopping, electrical isolation and any structural concern.
  • Replace the illustrative allowances with current quotations and an agreed scope before financial reliance.

Declaration

I confirm that this report records the visible condition, measurements, limitations and proposed next actions stated. It distinguishes observed facts from assumptions requiring lease, records or specialist review.

The report does not determine legal liability, code compliance or recoverable loss. Any change to scope, access, documents or opening-up evidence may require the findings and allowances to be revised.

Survey prepared and signed by

Avery Brooks

Avery Brooks - Commercial Building Inspector

Signed: 22 June 2026 - Reference MEC-2026-0620

Choose your store

Download DampApp Pro

Choose the store for your device. The app is free to download and use, with optional paid Pro features.

Download DampApp Pro on the App StoreGet DampApp Pro on Google Play

Choose your store

Download PropertySurvey Pro

Choose the store for your device. The app is free to download and use, with optional paid Pro features.

Download PropertySurvey Pro on the App StoreGet PropertySurvey Pro on Google Play

Choose your store

Download HousingSurvey Pro

Choose the store for your device. The app is free to install. Signing in requires an active HousingSurvey Pro organisation subscription purchased on the web.

Download HousingSurvey Pro on the App StoreGet HousingSurvey Pro on Google Play